Install Instructions
R
B-122-E
OPERATION
The Model RB-122-E Low Water Cut-Off is specifically designed
to provide burner cut-off if there is an unsafe water loss, which
can result from a broken or leaking radiator or pipe, or a
cracked section in the boiler.
Model RB-122-E
Conductance Type
Low Water Cut-Offs
For Residential Hot Water Boilers
®
• Before using product, read and understand instructions.
• Save these instructions for future reference.
• All work must be performed by qualified personnel trained in the proper application,
installation, and maintenance of HVAC systems in accordance with all applicable codes
and ordinances.
• Boiler manufacturer schematics should always be followed. In the event that the boiler
manufacturer’s schematic does not exist, or is not available from the boiler manufacturer,
refer to the schematics provided in this document.
• To prevent serious burns, the boiler must be cooled to 80˚F (27˚C) and the pressure must
be 0 psi (0 bar) before servicing.
• To prevent dry fire, which could cause a fire, there must be a 2" (51mm) minimum
width in the boiler section or 14" (32mm) pipe inner diameter for probe installation and
operation.
• The probe control must be connected in series with all other boiler operating and
safety controls.
• We recommend that secondary (redundant) Low Water Cut-Off controls be installed on all
steam boilers with heat input greater than 400,000 BTU/hour or operating above 15 psi
steam pressure. At least two controls should be connected in series with the burner
control circuit to provide safety redundancy protection should the boiler experience a
low-water condition. Moreover, at each annual outage, the low water cutoffs should be
dismantled, inspected, cleaned, and checked for proper calibration and performance.
• To prevent an electrical fire or equipment damage, electrical wiring insulation must have a
rating of 167˚F (75˚C) if the liquid’s temperature exceeds 180˚F (82˚C).
Failure to follow this warning could cause property damage, personal injury or death.
WARNING
CAUTION
!
WARNING
Requires 120 VAC power supply and can switch 120 VAC
or 24 VAC burner control circuits
McDonnell & Miller
Installation & Maintenance
Instructions
MM-238(H)