Install Instructions

5
D
FLUID FLOW
D= PIPE DIAMETER
1" PIPE
CONNECTION
5 x D
MINIMUM
5 x D
MINIMUM
a. The flow switch must be installed in the pipe using
a threaded tee connection or welding fitting of
minimum length such as a half coupling. Use a
face or hex bushing to reduce the tee outlet to 1"
pipe thread if a reduced tee outlet thread size fitting
is not available.
1" MAX
(25mm)
Paddle Arm
b. When installing brazed/soldered copper pipe,
size the threaded adapter to ensure the paddle
arm extends into the main run of the pipe.
The flow switch
should be located in a horizontal
section of pipe
where there is a straight horizontal
run of at least 5 pipe diameters on each side of the
flow switch. The flow switch may be installed in a
vertical pipe if the flow is in the upward direction.
The flow switch
must be installed in the upright
position
as shown with arrow mark on side of casting
in the same direction as fluid will flow.
Some system conditions that require more than 5 pipe
diameters are high viscosity fluid and high fluid velocity.
The flow switch must be installed in the pump suction
piping when spring-loaded check valves and/or other
close coupled accessories are installed in the pump
discharge piping.
1" (25mm)
2"
(50mm)
1
1
/4"
(32mm)
1
1
/2"
(40mm)
1
1
/4"
(32mm)
2"
(50mm)
1
1
/2"
(40mm)
FACE OR HEX.
BUSHING
2" (50mm)
3" (80mm)
2" (50mm)
3" (80mm)
1
1
/4" (32mm) 1
1
/4" (32mm)
1
1
/2" (40mm) 1
1
/2" (40mm)
2
1
/2" (65mm) 2
1
/2" (65mm)
2" (50mm)
3" (80mm)
1" MAX
(25mm)
1" (25mm)
4" (100mm)
6" (150mm)
2" (50mm)
3" (80mm)
4" (100mm)
6" (150mm)
2
1
/2" (65mm) 2
1
/2" (65mm)
Threaded
Pipe
Threaded
Pipe
CORRECT
INCORRECT
Threaded
Pipe
Welded
Pipe
STEP 2 - Determine the Location of the Flow Switch
STEP 3 - Connecting the Flow Switch to Pipe
a. Insert the 8/32 x 5/16" screw through lock washer, new larger
washer and paddle. Attach screw to the paddle arm and tighten
to a torque of approximately 12-16 lb•in (1.36-1.81 N•m).
NOTE: If two paddles are being installed, they must be stacked one on top
of the other with the longer paddle first in line to the flow.