Install Instructions

Series FS8-W
General Purpose
Liquid Flow Switch
OPERATION
This control is an independently mounted water flow
sensing device that makes or breaks an electrical
circuit when flow stops or starts.
• Before using product, read and understand instructions.
• Save these instructions for future reference.
All work must be performed by qualified personnel trained in the proper application,
installation, and maintenance of plumbing, steam and electrical equipment and/or systems in
accordance with all applicable codes and ordinances.
To prevent electrical shock, turn off the electrical power before making electrical
connections.
To prevent an electrical fire or equipment damage, electrical wiring insulation must have a
rating of 167˚F (75˚C) if the liquid’s temperature exceeds 180˚F (82˚C).
To prevent electrocution, when the electrical power is connected to the flow switch, do not
touch the terminals.
Make sure flow switch electrical cover is secured before turning on electric power.
Failure to follow this warning could cause property damage, personal injury or death.
W
ARNING
CAUTION
!
WARNING
Series FS8-W
Now
with
Stainless Steel
Paddles
McDonnell & Miller
Installation & Maintenance
Instructions
MM-600(G)