a. Cover Removal and Installation Procedure
For FS6 models with NEMA 1 Enclosure
Using a flathead screwdriver, loosen but do not
remove the two cover screws and remove the cover
(A).
Place the cover on the flow switch sliding the slots
behind the two loose cover screws. Push the cover
down into the flow switch and using a flat blade
screwdriver, tighten the cover screws to a torque of
10 lb•in (1.13 N•m).
For FS6-W models with NEMA 4X Enclosure
Using flathead screwdriver, unscrew the six cover
screws and remove cover.
Place the electrical connection cover on the flow
switch and insert the six cover screws. Tighten the
screws to a torque of 10 lb•in (1.13 N•m).
STEP 3 - Electrical Installation
To prevent electrical shock, turn off the electrical power before making electrical connections.
To prevent an electrical fire or equipment damage, electrical wiring insulation must have a rating of
167˚F (75˚C) if the liquid’s temperature exceeds 180˚F (82˚C).
To prevent electrocution, when the electrical power is connected to the flow switch, do not touch the
terminals.
Make sure flow switch electrical cover is secured before turning on electric power.
Failure to follow this warning could cause property damage, personal injury or death.
!
WARNING
b. Electrical Conduit Connection
Connect electric conduit to flow switch electrical enclosure.
Follow accepted electrical practices when installing fittings
and making connections.
Refer to and follow local codes and standards when
selecting the types of electrical fittings and conduit to
connect to flow switch.