Install Instructions

FLOW RATES
Flow rates required to activate flow switch are shown
in chart below. The values are calculated for sensing
water (potable, non-polluted) in a horizontal pipe.
Settings will vary when used to sense flow of other
fluids.
3
NOTE: DO NOT USE LIQUID FLOW
SWITCHES ON SYSTEMS WITH
FLOW VELOCITY GREATER THAN
10 FEET (3M) PER SECOND.
INSTALLATION
STEP 1 - Determine the Location of the Flow Switch
Fluid Flow
3/4" or 1"
PIPE
5 x D
MINIMUM
D
D= PIPE DIAMETER
5 x D
MINIMUM
The flow switch should be located in a horizontal
section of pipe where there is a straight horizontal run
of at least 5 pipe diameters on each side of the flow
switch.
The flow switch must be installed in the upright
position as shown with arrow mark on side of casting
in the same direction as fluid will flow.
Some system conditions that require more than 5 pipe
diameters are high viscosity fluid and high fluid velocity.
The flow switch should be installed in the pump suction
piping when spring-loaded check valves and/or other
close coupled accessories are installed in the pump
discharge piping.
Flow Rates
Pipe
Mode of Operation
Size NPT Flow No Flow
in. (mm) Settings gpm (lpm) gpm (lpm)
3
4
(20)
Factory or
or Minimum 1.5 (5.7) 1.1 (4.2) 16.62 (63)
1 (25)
Maximum 15 (56.8) 10 (37.9) 27 (102)
Values are ± 10%
Max. Flow
Rate gpm
(lpm) w/o
Paddle Damage