Specifications

Product Specifications
A-5
Product Specifications
Heat Dissipation
McDATA products have the following maximum heat dissipation
characteristics:
Intrepid 6064 Director: 490 watts (1,672 BTU/hr).
Intrepid 6140 Director: 841 watts (2,873 BTU/hr).
Intrepid 10000 Director: 2,496 watts (8,517 BTU/hr).
Sphereon 3232 Fabric Switch: 245 watts (836 BTU/hr).
Sphereon 4300 Fabric Switch: 37 watts (127 BTU/hr).
Sphereon 4400 Fabric Switch: 36 watts (123 BTU/hr).
Sphereon 4500 Fabric Switch: 49 watts (167 BTU/hr).
Sphereon 4700 Fabric Switch: 71 watts (242 BTU/hr).
Eclipse 1620 SAN Router: 73 watts (249 BTU/hr).
Eclipse 2640 SAN Router: 198 watts (676 BTU/hr).
Clearances
McDATA products have the following cooling airflow clearances. In
addition, the Intrepid 10000 Director may require removal from an
equipment cabinet (left-side service clearance required) for FRU
removal and replacement.
Intrepid 6064 and 10000 Directors:
Right and left side: 5.1 centimeters (2.0 inches).
Front and rear: 7.6 centimeters (3.0 inches).
Top and bottom: No clearance required.
NOTE: If the Intrepid 10000 Director is installed in a non-McDATA
equipment cabinet with a door that does not provide direct airflow
over the full height of the unit, 17.8 centimeters (7.0 inches) of front
clearance is required.
Intrepid 6140 Director:
Right and left side: 2.5 centimeters (1.0 inches).
Front and rear: 7.6 centimeters (3.0 inches).
Top and bottom: No clearance required.