NOTE: If multiple products and themanagement server are delivered in
a Fabricenter equipment cabinet, all devices are configured with unique
IP addresses that do not require change. The addresses require change
only if multiple cabinets are LAN-connected.
Subnetmask - The default subnetmaskis 255.0.0.0.Ifthedirector
is installed on a complex public LAN with one or more routers,
theaddressmayrequirechange.
Gateway address - The default gateway address is 0.0.0.0.Ifthe
director is installed on a public LAN, the gateway address must
be changed to the address of the corporate intranet local router.
Verify the LAN installation with the customer. If one director is
installed on a dedicated LAN, network addresses do not require
change.Go toTask 6: Unpack, Inspect, and Installthe ManagementServer
on page 2-34.
If multiple products are installed or a public LAN segment is used,
network addresses must bechanged to conform to the customer LAN
addressing plan. Perform the following steps to change a product IP
address, subnet mask, or gateway address. An asynchronous RS-232
modem cable and maintenance terminal (desktop or notebook PC)
with a Windows-based operating system and RS-232 serial
communication software (such as ProComm Plus or HyperTerminal)
are required.
1. Using a Phillips screwdriver, remove the protective cap from the
9-pin maintenance port. Connect one end of the RS-232 modem
cable to the port.
2. Connect the other cable end to a 9-pin serial communication port
(COM1 or COM2) at the rear of the maintenance terminal PC.
3. Power on the maintenance terminal. At the Windows desktop,
click Startattheleftsideofthetaskbar.TheWindows Workstation
menu displays.
NOTE: The following steps describe changing network addresses using
HyperTerminal serial communication software.
4. At the Windows Workstation menu, sequentially select the
Programs, Accessories, Communications,andHyperTerminal options.
The Connection Description dialog box displays (Figure 2-15).