Intrepid® 6064 Director Installation and Service Manual
General Information
Power Module
Assembly
The power module assembly is located at the bottom rear of the
director. The module is a nonconcurrent FRU, and the director must
be powered off prior to scheduled removal and replacement. The
module provides:
• Two single-phase AC power connectors. Each connector is input
rated at 85 to 264 VAC.
• A power switch (circuit breaker) that controls AC power
distribution to both power supplies. The breaker is set manually,
or isautomatically trippedby internal softwareif thermal sensors
indicate the director is overheated.
• A 9-pin maintenance port that provides a connection for a local
terminalordial-in connection fora remote terminal. Although the
port is typically used by maintenance personnel, operations
personnel use the port to configure network addresses.
• An input filter and AC system harness (internal to the FRU) that
provides the wiring to connect the AC power connectors to the
power switch and power supplies (through the backplane).
Fan Module
Two fan modules, each containing three fans (six fans total), provide
cooling for director FRUs, as well as redundancy for continued
operationifafanfails.
A fan module can be replaced while the director is powered on and
operating, provided the module is replaced within ten minutes (after
whichsoftwarepowersoffthedirector).AnamberLEDforeachfan
module illuminates if one or more fans fail or rotate at insufficient
angular velocity.
SBAR Assembly
The directoris delivered with twoSBAR assemblies. Theactive SBAR
isresponsibleforFibreChannelframetransmissionfromany director
port to any other director port. Connections are established without
software intervention. The assembly accepts a connection request
from a port, determines if a connection can be established, and
establishes the connection if the destination port is available. The
assembly also stores busy, source connection, and error status for
each director port.
The backup SBAR takes over operation if the active assembly fails,
and provides the ability to maintain connectivity and data frame