Service manual

5
RRP: Fan Module
5-33
Removal and Replacement Procedures (RRPs)
RRP: Fan Module
Use the following procedures to remove or replace a fan module. A
list of tools required is provided.
Tools Required The following tools are required to perform these procedures.
Door key with 5/16-inch socket (provided with the FC-512
Fabricenter equipment cabinet).
Standard flat-tip screwdriver.
ESD grounding cable and wrist strap.
Removal To remove a fan module:
1. If the director is installed in a stand-alone configuration, go to
step 2. If the director is rack-mounted, perform one of the
following:
If the director is installed in a McDATA-supplied FC-512
Fabricenter equipment cabinet, insert the 5/16" door tool into
the socket hole at the right top of the rear door. Turn the tool
counter-clockwise to unlock and open the door.
If the director is installed in a customer-supplied equipment
cabinet, unlock and open the cabinet rear door as directed by
the customer representative.
2. Follow ESD procedures by attaching a wrist strap to the director
chassis and your wrist (Figure 5-2).
ATTENTION! To avoidcausing machine errorsor damagewhileworkingon
the director, follow ESD procedures by connecting a grounding cable to the
director chassis and wearingan ESD wrist strap.
3. Remove the RFI shield (RRP: RFI Shield on page 5-28).
4. Identify the defective fan module from the amber LED on the
module or failure information at the management server
Hardware View.
5. Two captive screws secure the fan module to the director chassis
(Figure 5-11). Using a standard flat-tip screwdriver, loosen the
captive screws.