Service manual

5
5-16
Intrepid® 6064 Director Installation and Service Manual
Removal and Replacement Procedures (RRPs)
b. Insert the torque tool into the locking Allen screw at the
bottom of the card. Turn the torque tool clockwise until you
feel it release and hear a clicking sound. As the screw turns
clockwise, the card locks into place.
c. Verify the card stiffener is flush with the front of the card cage
andevenwithotherdirectorlogiccards.
4. Performan externalloopbacktestforall ports on thereplacement
port card (Performing Loopback Tests on page 4-21).If the test fails,
go toChapter 3,MaintenanceAnalysisProcedures(MAPS)toisolate
the problem.
5. Reconnect a fiber-optic jumper cable to each port on the card as
follows.Inspectthelabelon thejumpercable toensurethecorrect
connection. Repeat this step for all four ports.
a. Remove the protective cap from the cable connector and the
protective plug from the portopticaltransceiver. Store the cap
and plug in a suitable location for safekeeping.
b. Clean the cable and port connectors (Cleaning Fiber-Optic
Components on page 4-40).
c. Insert the keyed LC cable connector into port optical transceiver.
6. Disconnect the ESD wrist strap from thedirector chassis and your
wrist.
7. Inspect the port card to ensure all amber LEDs are extinguished.
If any amber LEDs are illuminated, go to Chapter 3, Maintenance
Analysis Procedures (MAPS) to isolate the problem.
8. At the management server or at a web browser connected to the
EFCM Basic Edition interface, inspect the Event Log.Ensurethe
following event codes appear in the log:
500 - Port card hot-insertion initiated.
501 - Port card has been recognized.
If an event code 501 does not appear in the log, go to Chapter 3,
MaintenanceAnalysisProcedures(MAPS)to isolate the problem.
9. At the Hardware View, double-click the graphic representing the
replacement card to open the Port Card View.AtthePort Card
View:
a. Ensure no alert symbols appear that indicate a failure
(yellow triangle or red diamond).