Service manual
3
3-44
Intrepid® 6064 Director Installation and Service Manual
Maintenance Analysis Procedures (MAPS)
Figure 3-2 UPM Card Diagram (OSI)
Figure 3-3 UPM Card Diagram (FICON)
• Replace the transceiver with a transceiver of the same type
(shortwave or longwave) and speed.
• Perform an external loopback test (
Performing Loopback Tests
on page 4-21).
NOTE: Event code 514 may generate a call-home event that incorrectly
indicates a CTP card failure. Although the optical socket on the CTP card may
have failed, replace the transceiver and verify operation. If a failure is still
indicated, replace the CTP card (
RRP: CTP Card
on page 5-6).
Was the maintenance action successful?
NO YES
↓ The product port is operational. Exit MAP.
21
A port card failed and the card must be replaced (
RRP: Port Module
Card (UPM and XPM)
on page 5-11).
• This procedure is concurrent and can be performed while
director power is on.