Service manual

2
2-10
Intrepid® 6140 Director Installation and Service Manual
Installation Tasks
3. Locate the rack-mount position. The director is 20 inches (12 U)
high.
4. Verify all FRUs, including the SFP and XFP optical transceivers,
logic cards, fans, and power supplies are installed as ordered.
5. Open the rack-mount kit and inspect the contents. Refer to the
enclosed bill of materials and verify all parts are delivered.
6. Using installation instructions delivered with the rack-mount kit
and a #2Phillipsscrewdriver, install thedirector inthe equipment
cabinet.
DANGER
Use the supplied power cords. Ensure the facility power receptacle is
the correct type, supplies the required voltage, and is properly
grounded.
7. ConnecttheU.S.ACpowercordstotheright(PS0)andleft(PS1)
receptacles at the rear of the director (Figure 2-3).
8. Connect the remaining ends of the AC power cords to separate
(for redundancy) rack power strips.
NOTE: The director does not have a power switch. Therefore the director
powers on when its power cords are connected to facility or rack power.
Figure 2-3 AC Power Connections (Director)
9. Connect the equipment rack power cords to separate (for
redundancy)facilitypower sourcesthatprovidesingle-phase, 180
to 264 VAC voltage.