Thermal Events (800 through 899)
A-69
Event Code Tables
Event Code: 806
Message: Critically hot temperature warning (SBAR thermal sensor).
Severity: Major.
Explanation: The thermal sensor associated with an SBAR indicates the hot temperature threshold was reached or exceeded.
Action: Replace the indicated SBAR with a functional assembly. Perform the data collection procedure and return the CD
and faulty assembly to McDATA support personnel.
Event Data: No supplementary data included with this event.
Distribution: Director Management Server Host
Nonvolatile
System
Event Log
System
Error LED
Event Log E-Mail Call-Home Sense Info Link Incident
Event Code: 807
Message: SBAR shutdown due to thermal violation.
Severity: Major.
Explanation: An SBAR failed and was powered off because of excessive heat. This event follows an indication that the hot
temperature threshold was reached or exceeded (event code 806). If the active SBAR fails, the backup SBAR
takes over operation. If the backup SBAR fails, the active SBAR is not impacted.
Action: Replace the failed SBAR with a functional assembly. Perform the data collection procedure and return the CD
and faulty assembly to McDATA support personnel.
Event Data: No supplementary data included with this event.
Distribution: Director Management Server Host
Nonvolatile
System
Event Log
System
Error LED
Event Log E-Mail Call-Home Sense Info Link Incident