Service manual
A
Power Supply Events (200 through 299)
A-29
Event Code Tables
Event Code: 207
Message: Power supply installed.
Severity: Informational.
Explanation: A redundant power supply was installed with the director powered on and operational. Both power supplies adjust
to share operating load for the director.
Action: No action required.
Event Data: No supplementary data included with the event.
Distribution: Director Management Server Host
Nonvolatile
System
Event Log
System
Error LED
Event Log E-Mail Call-Home Sense Info Link Incident
Event Code: 208
Message: Power supply false shutdown.
Severity: Major.
Explanation: Director operational firmware nearly shut down the indicated power supply as a result of failure or facility power
loss or voltage fluctuation.
Action: Confirm operation of facility power. If subsequent power loss events occur, replace the failed power supply.
Perform the data collection procedure and return the CD and failed power supply to McDATA support personnel.
Event Data: No supplementary data included with this event.
Distribution: Director Management Server Host
Nonvolatile
System
Event Log
System
Error LED
Event Log E-Mail Call-Home Sense Info Link Incident