Intrepid® 6140 Director Installation and Service Manual
Removal and Replacement Procedures (RRPs)
7. Replace the RFI shield.
8. At the management server or at a web browser connected to the
EFCM Basic Edition interface, inspect the Event Log.Ensurethe
following event codes appear in the log:
600 - SBAR card hot-insertion initiated.
601 - SBAR card hot-insertion completed.
If an event code 601 does not appear in the log, go to Chapter3,
MaintenanceAnalysisProcedures(MAPS)to isolate the problem.
9. Perform one of the following to verify SBAR operation:
If at the management server, open the Hardware View and
observe the SBAR graphic to ensureno alert symbols appear
that indicate a failure (yellow triangle or red diamond). If a
problem is indicated, go to Chapter 3, Maintenance Analysis
Procedures (MAPS) to isolate the problem.
If at a web browser connected to the EFCM Basic Edition
interface, open the Switch tab at the View panel and ensure no
amber LEDs illuminate that indicate an SBAR failure. If a
problem is indicated, go to Chapter 3, Maintenance Analysis
Procedures (MAPS) to isolate the problem.
10. Perform the data collection procedure (Collecting Maintenance
Data on page 4-32).
11. If the customer requests the replacementSBAR assembly beset as
the active SBAR, perform a FRU switchover. At the Hardware
View, right-click the graphic representing the replacement
assembly to open a menu, then select Switchover.
12. Perform one of the following to clear the system error (ERR) LED:
If at the management server, open the Hardware View and:
a. Right-click the front panel bezel graphic (away from a
FRU) to open a menu.
b. Click the Clear System Error Light menu selection.
If at a web browser connected to the EFCM Basic Edition
interface:
a. Click the Switch tab at the Operations panel. The Operations
panel opens with the Switch page displayed.