Intrepid® 6140 Director Installation and Service Manual
Removal and Replacement Procedures (RRPs)
RRP: SBAR Assembly
Use the following procedures to remove or replace an SBAR
assembly. A list of tools required is provided.
Tools Required The following tools are required to perform these procedures.
Door key with 5/16-inch socket (provided with the FC-512
Fabricenter equipment cabinet).
Standard flat-tip screwdriver.
ESD grounding cable and wrist strap.
Torque tool and hex adapter (provided with the director).
Removal To remove an SBAR assembly:
1. If the director is installed in a stand-alone configuration, go to
step 3. If the director is rack-mounted, perform one of the
following:
If the director is installed in a McDATA-supplied FC-512
Fabricenter equipment cabinet, insert the 5/16" door tool into
the socket hole at the right top of the rear door. Turn the tool
counter-clockwise to unlock and open the door.
If the director is installed in a customer-supplied equipment
cabinet, unlock and open the cabinet rear door as directed by
the customer representative.
2. Remove the RFI shield.
ATTENTION! To avoidcausing machine errorsor damagewhileworkingon
the director, follow ESD procedures by connecting a grounding cable to the
director chassis and wearingan ESD wrist strap.
3. Follow ESD procedures by attaching a wrist strap to the director
chassis and your wrist (Figure 5-1).
4. Identify the defective SBAR assembly from the amber LED on the
assembly or failure information at the management server
Hardware View.
5. The SBAR assembly is secured to the director backplane withtwo
handles(extractor levers)that snaplock (Figure 5-10). Open both
handles.