Intrepid® 6140 Director Installation and Service Manual
Removal and Replacement Procedures (RRPs)
RRP: Power/System Error LED Assembly
Use the following procedures to remove or replace the
Power/System Error LED assembly. A list of tools required is
provided.
Tools Required The following tools are required to perform these procedures.
• Door key with 5/16-inch socket (provided with the FC-512
Fabricenter equipment cabinet).
• Standard flat-tip screwdriver.
• ESD grounding cable and wrist strap.
Removal To remove the Power/System Error LED assembly:
1. Remove the RFI shield.
ATTENTION! To avoidcausing machine errorsor damagewhileworkingon
the director, follow ESD procedures by connecting a grounding cable to the
director chassis and wearingan ESD wrist strap.
2. Follow ESD procedures by attaching a wrist strap to the director
chassis and your wrist (Figure 5-1).
3. Remove only the center and upper left fan modules (viewed from
the rear) (RRP: Fan Module on page 5-30).
4. Unplug the Power/System LED assembly cable from the
backplane.
5. Remove the Power/System LED assembly (Figure 5-9).
6. Place the LED assembly in an anti-static bag to provide ESD
protection.