5
5-28
Intrepid® 6140 Director Installation and Service Manual
Removal and Replacement Procedures (RRPs)
3. Position the AC module at the rear of the director chassis
(Figure 5-7).Pushthemoduletowardthebackplanetoengagethe
connector pins.
4. Insert andtighten the two panhead Phillips screws that secure the
AC module.
5. Replace the power supply (RRP: Power Supply on page 5-23).
6. Disconnect the ESD wrist strap from thedirector chassis and your
wrist.
7. Connect the power cord to the AC module.
8. Verify that power-on self-tests (POSTs) complete and the green
power LED on the front bezel, green LED on the active CTP card,
and green PWR OK LEDs on both power supplies remain
illuminated. If a problem is indicated, go to Chapter 3,
MaintenanceAnalysisProcedures(MAPS)to isolate the problem.
9. Perform one of the following to verify AC module operation:
If at the management server, open the Hardware View and
observe the AC module graphics to ensure no alert symbols
appearthat indicate afailure(yellow triangleor red diamond).
Ifa problemis indicated, goto Chapter3, Maintenance Analysis
Procedures (MAPS) to isolate the problem.
If at a web browser connected to the EFCM Basic Edition
interface, open the Switch tab at the View panel and ensure no
amber LEDs illuminate that indicate FRU failure. If a problem
is indicated, go to Chapter 3, Maintenance Analysis Procedures
(MAPS) to isolate the problem.
10. Perform the data collection procedure (Collecting Maintenance
Data on page 4-32).
11. Perform one of the following to clear the system error (ERR) LED:
If at the management server, open the Hardware View and:
a. Right-click the front panel bezel graphic (away from a
FRU) to open a menu.
b. Click the Clear System Error Light menu selection.
If at a web browser connected to the EFCM Basic Edition
interface:
a. Click the Switch tab at the Operations panel. The Operations
panel opens with the Switch page displayed.