Service manual
5
RRP: Power Supply
5-25
Removal and Replacement Procedures (RRPs)
5. Inspect the power supply to ensure the green PWR OK LED is
illuminated and all amber LEDs are extinguished. If a problem is
indicated, go to Chapter 3, Maintenance Analysis Procedures
(MAPS) to isolate the problem.
6. At the management server or at a web browser connected to the
EFCM Basic Edition interface, inspect the Event Log.Ensurean
event code 207 (power supply installed) appears in the log.
If an event code 207 does not appear in the log, go to Chapter3,
MaintenanceAnalysisProcedures(MAPS)to isolate the problem.
7. Perform one of the following to verify power supply operation:
— If at the management server, open the Hardware View and
observe the power supply graphic to ensure no alert symbols
appearthat indicate afailure(yellow triangleorreddiamond).
Ifa problemis indicated, goto Chapter3, Maintenance Analysis
Procedures (MAPS) to isolate the problem.
— If at a web browser connected to the EFCM Basic Edition
interface, open the Switch tab at the View panel and ensure no
amber LEDs illuminate that indicate a power supply failure. If
a problem is indicated, go to Chapter 3, Maintenance Analysis
Procedures (MAPS) to isolate the problem.
8. Perform the data collection procedure (Collecting Maintenance
Data on page 4-32).
9. Perform one of the following to clear the system error (ERR) LED:
— If at the management server, open the Hardware View and:
a. Right-click the front panel bezel graphic (away from a
FRU) to open a menu.
b. Click the Clear System Error Light menu selection.
— If at a web browser connected to the EFCM Basic Edition
interface:
a. Click the Switch tab at the Operations panel. The Operations
panel opens with the Switch page displayed.
b. Click the Sys Err Light tab. The Switch page displays with
the Sys Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
10. If necessary, close and lock the equipment cabinet door.