Intrepid® 6140 Director Installation and Service Manual
Removal and Replacement Procedures (RRPs)
10. Restore communication to the port with the replacement
transceiver as directed by the customer (Blocking and Unblocking
Ports on page 4-27). Inform the customer the port is available for use.
11. Perform one of the following to clear the system error (ERR) LED:
If at the management server, open the Hardware View and:
a. Right-click the front panel bezel graphic (away from a
FRU) to open a menu.
b. Click the Clear System Error Light menu selection.
If at a web browser connected to the EFCM Basic Edition
interface:
a. Click the Switch tab at the Operations panel. The Operations
panel opens with the Switch page displayed.
b. Click the Sys Err Light tab. The Switch page displays with
the Sys Err Light tab selected. A System Error Light is ON
message displays on the page.
c. Click Clear Light.
12. If necessary, close and lock the equipment cabinet door.