Intrepid® 6140 Director Installation and Service Manual
Repair Information
— The director-to-management server Ethernet link drops
momentarily and the following occur at the Hardware View:
• As the network connection drops, the Intrepid 6140 Status
table turns yellow, the Status field displays No Link,and
the State field displays Link Timeout.
• The status bar at the bottom of the window displays a grey
square, indicating director status is unknown.
• Illustrated FRUs disappear, and appear again as the
connection is re-established.
Cleaning Fiber-Optic Components
Perform this procedure as directed in this publication and when
connecting or disconnecting fiber-optic cables from port optical
transceivers.
Tools required:
• ESD grounding cable and wrist strap
• Fiber-optic cleaning kit with:
— Oil-free compressed air or HFC-134a aerosol duster
— Alcohol-soaked cleaning pads.
Procedure:
CAUTION
Wear eye protection when using an aerosol duster.
To clean fiber-optic components:
ATTENTION! To avoidcausing machine errorsor damagewhileworkingon
the director, follow ESD procedures by connecting a grounding cable to the
director chassis and wearingan ESD wrist strap.
1. Follow ESD procedures by attaching a wrist strap to the director
chassis and your wrist.
2. Disconnect the fiber-optic cable from the port. Use an aerosol
duster to blow away any contaminants from the connector (part
A of Figure 4-13).