IML, IPL, or Reset the Director
4-39
Repair Information
— The status bar at the bottom of the window displays a grey
square, indicating director status is unknown.
— Illustrated FRUs disappear, and appear again as the
connection is re-established.
IPL the Director (Element Manager Application)
To IPL the director from the Element Manager application:
1. At the Element Manager application, select the IPL option from
the Maintenance menu. An Information dialog box displays.
2. Click Yes to IPL the director. During theIPL, the
director-to-management server Ethernet link drops momentarily
and the following occur at the Hardware View:
— Asthe networkconnectiondrops,theIntrepid6140Statustable
turns yellow, the Status field displays No Link,andtheState
field displays Link Timeout.
— The status bar at the bottom of the window displays a grey
square, indicating director status is unknown.
— Illustrated FRUs disappear, and appear again as the
connection is re-established.
Reset the Director (CTP Front Panel)
To reset the director from the CTP front panel:
1. Press and hold the RESET button for approximately three
seconds.
2. During the reset:
—Thegreenpower(PWR) LED on the director front panel
illuminates.
—Theambersystemerror(ERR) LED onthe directorfront panel
blinks momentarily while the director is tested.
— The green LEDs associated with the Ethernet port blink
momentarily while the port is tested.
— The amber LEDs associated with the ports blink momentarily
while the ports are tested.