Service manual

Maintenance Analysis Procedures
3-33
Maintenence Analysis Procedures
7
An SBAR assembly is not recognized by director firmware because
the firmware version is not supported or the SBAR assembly failed.
Advise the customer of the problem and determine the correct
firmware version to download.
Download the firmware (
Downloading Director Firmware and
Software
on page 4-41). Perform a data collection after the download
(
Collecting Maintenance Data
on page 4-32).
Did the firmware download solve the problem?
NO YES
The director appears operational. Exit MAP.
8
Visual inspection (amber LED illuminated) or event codes indicate an
SBAR assembly failed.
Replace the SBAR assembly (
RRP: SBAR Assembly
on page 5-36).
The procedure is concurrent and performed while the product is
operational.
Perform a data collection as part of FRU replacement (
Collecting
Maintenance Data
on page 4-32).
Was the maintenance action successful?
YES NO
Contact the next level of support. Exit MAP.
The product is operational. Exit MAP.