Service manual
3-32
Intrepid® 6140 Director Installation and Service Manual
Maintenence Analysis Procedures
YES NO
↓ Contact the next level of support. Exit MAP.
The product is operational. Exit MAP.
4
An intermittent synchronous dynamic random access memory
(SDRAM) problem may indicate a CTP card failure.
Is the event code a recurring problem?
NO YES
↓ A CTP card failure is indicated. Go to step 6.
Perform a data collection (
Collecting Maintenance Data
on
page 4-32) and contact the next level of support. Exit MAP.
5
An intermittent thermal problem may indicate a CTP card failure.
Reset the director (
IML, IPL, or Reset the Director
on page 4-38).
Was the maintenance action successful?
NO YES
↓ The product is operational. Exit MAP.
6
Visual inspection (amber LED illuminated) or event codes indicate a
CTP card failed.
Replace the CTP card (
RRP: CTP Card
on page 5-6).
• The procedure is concurrent and performed while the product is
operational.
• Perform a data collection as part of FRU replacement (
Collecting
Maintenance Data
on page 4-32).
NOTE: Do not remove a CTP card if the backup CTP card is not fully
operational and director power is on; otherwise the director IP address,
configuration data, and other operating parameters will be lost.
Was the maintenance action successful?
YES NO
↓ Contact the next level of support. Exit MAP.
The product is operational. Exit MAP.