Service manual
Maintenance Analysis Procedures
3-9
Maintenence Analysis Procedures
Are any amber LEDs illuminated?
NO YES
↓ A FRU failure, power-on self-test (POST) failure, link incident,
interswitch link (ISL) problem, fenced E_Port, or segmented
E_Port is indicated. To obtain event codes that identify the
failure, go to step 10.
4
Is the product management interface (browser PC, management
server, or OSI host console) powered on and operational?
NO YES
↓ Go to step 7.
5
Power on the management interface platform and launch the
associated management application:
• EFCM Basic Edition - (
Task 4: Configure Director at the EFCM
Basic Edition Interface (Optional)
on page 2-11).
• SAN management application - (
Task 6: Unpack, Inspect, and
Install the Management Server
on page 2-34 and
Access the
Management Server Desktop
on page 2-38).
• OSI host console - Refer to documentation supplied with the
host system for instructions.
Was the maintenance action successful?
NO YES
↓ Go to step 7.
6
Inspect the management interface for communication link failure.
Observe one of the following:
•APage cannot be found, Unable to locate the server, HTTP
404 - file not found, or similar message (browser PC).