Universal Library User's Guide Analog Input Boards - CIO-DAS1400 and CIO-DAS1600 Series
79
CIO-DAS1400 and CIO-DAS1600 Series
Analog Input
Analog input functions and methods supported
UL: cbAIn(), cbAInScan(), cbATrig(), cbFileAInScan()
UL for .NET: AIn(), AInScan(), ATrig(),FileAInScan()
Analog input argument values
Options BACKGROUND, CONTINUOUS, EXTCLOCK, CONVERTDATA, SINGLEIO, DMAIO, BURSTMODE,
EXTTRIGGER
For CIO-DAS1600, the following argument values are also valid:
DTCONNECT, EXTMEMORY.
HighChan 0 to 15 in single-ended mode, 0 to 7 in differential mode
Rate DAS1401/12, DAS1402/12, DAS1601/12, DAS1602/12
160000
DAS1602/16, DAS1402/16
100000
DAS1401/12, DAS1402/12, DAS1601/12, DAS1602/12 to external memory
330000
Range CIO-DAS1402, CIO-DAS1602, CIO-DAS1402/16 and CIO-DAS1602/16
BIP10VOLTS UNI10VOLTS
BIP5VOLTS UNI5VOLTS
BIP2PT5VOLTS UNI2PT5VOLTS
BIP1PT25VOLTS UNI1PT25VOLTS
CIO-DAS1401 and CIO-DAS1601
BIP10VOLTS UNI10VOLTS
BIP1VOLTS UNI1VOLTS
BIPPT1VOLTS UNIPT1VOLTS
BIPPT01VOLTS UNIPT01VOLTS
Analog output (CIO-DAS1600 series only)
Analog output functions and methods supported
UL: cbAOut(), cbAOutScan()
UL for .NET: AOut(), AOutScan()
Analog output argument values
Options SIMULTANEOUS
HighChan 1 max
Count 2 max
Rate Ignored
Pacing Software pacing only
Range Analog output gain is not programmable, so the Range argument is ignored.
DataValue 0 to 4095