Technical Literature

6
BLOWER PERFORMANCE PGC2TC/TL CONTINUED
PGC2TC/TL - 95.1% AFUE, Two Stage Gas Furnace
Model Number
&
Heating Input
(Btuh)
Motor Switch Settings
(0 = OFF, 1 = ON)
External Static Pressure (in.W.C.)
0.1 0.2 0.3 0.4 0.5 0.6 0.7 0.8
1/5 2/6 3/7 4/8 CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise CFM Rise
*TC / TL - 100D
- 35C
(100,000)
0 0 0 0 1,125
1,040
1 0 0 0 1,205
1,120
1,040
0 1 0 0 1,305
1,225
1,150
1,070
995
1 1 0 0 1,430 62 1,350 65 1,270
1,190
1,110
1,030
0 0 1 0 1,525 58 1,450 61 1,375 64 1,300
1,225
1,150
1,075
1,000
1 0 1 0 1,620 54 1,540 57 1,465 60 1,390 63 1,315
1,240
1,165
1,090
0 1 1 0 1,695 52 1,620 54 1,545 57 1,465 60 1,390 63 1,315
1,235
1,160
1 1 1 0 1,770 50 1,700 52 1,630 54 1,555 57 1,485 59 1,410 62 1,340
1,265
0 0 0 1 1,875 47 1,805 49 1,730 51 1,655 53 1,580 56 1,510 58 1,435 61 1,340
1 0 0 1 1,905 46 1,840 48 1,775 50 1,710 51 1,640 54 1,575 56 1,510 58 1,445 61
0 1 0 1 1,980 44 1,910 46 1,845 48 1,780 49 1,715 51 1,650 53 1,580 56 1,515 58
1 1 0 1 2,025 43 1,960 45 1,895 46 1,830 48 1,765 50 1,700 52 1,635 54 1,570 56
0 0 1 1 2,085 42 2,025 43 1,960 45 1,900 46 1,840 48 1,775 50 1,715 51 1,655 53
1 0 1 1 2,135 41 2,070 42 2,010 44 1,945 45 1,880 47 1,815 48 1,750 50 1,685 52
0 1 1 1 2,200 40 2,145 41 2,090 42 2,035 43 1,980 44 1,925 46 1,870 47 1,820 48
1 1 1 1 2,280 39 2,225 40 2,170 41 2,115 42 2,065 43 2,010 44 1,955 45 1,900 46
*TC / TL - 120D
- 45D
(120,000)
0 0 0 0 1,395
1,350
1,305
1,260
1,210
1,165
1,120
1 0 0 0 1,465
1,420
1,375
1,330
1,290
1,245
1,200
1,155
0 1 0 0 1,555 68 1,510 70 1,470
1,425
1,380
1,340
1,295
1,250
1 1 0 0 1,625 65 1,585 67 1,540 69 1,500 70 1,460
1,415
1,375
1,335
0 0 1 0 1,690 62 1,650 64 1,610 66 1,570 67 1,530 69 1,485
1,445
1,405
1 0 1 0 1,760 60 1,715 62 1,670 63 1,625 65 1,575 67 1,530 69 1,485
1,440
0 1 1 0 1,835 58 1,790 59 1,745 60 1,695 62 1,650 64 1,605 66 1,555 68 1,510 70
1 1 1 0 1,885 56 1,840 57 1,790 59 1,745 60 1,700 62 1,655 64 1,610 66 1,565 67
0 0 0 1 1,945 54 1,900 56 1,850 57 1,805 58 1,760 60 1,710 62 1,665 63 1,620 65
1 0 0 1 1,950 54 1,905 55 1,860 57 1,820 58 1,775 59 1,735 61 1,690 62 1,650 64
0 1 0 1 2,075 51 2,030 52 1,990 53 1,945 54 1,900 56 1,855 57 1,810 58 1,770 60
1 1 0 1 2,125 50 2,085 51 2,040 52 2,000 53 1,955 54 1,910 55 1,870 56 1,825 58
0 0 1 1 2,170 49 2,130 50 2,090 51 2,045 52 2,005 53 1,965 54 1,925 55 1,880 56
1 0 1 1 2,215 48 2,180 48 2,140 49 2,105 50 2,070 51 2,035 52 2,000 53 1,965 54
0 1 1 1
2,225 47 2,165 49 2,100 50 2,040 52
1 1 1 1
2,170 49 2,120 50 2,065 51
1. Motor Switch Settings are for heating speeds using HEAT switches 1, 2, 3, & 4 and cooling speeds using COOL switches 5, 6, 7, & 8.
2. Two openings are recommended for airflows above 1,600 CFM if the filter(s) is (are) adjacent to the furnace.
3. Data is shown without filter.
4. Temperature rises in the table are approximate. Actual temperature rises may vary
5. Cells shaded in gray indicate a temperature rise outside of the recommended range.
6. When in low stage, the circulating airflow is 70% of the tables high value (2-stage furnaces only).