Product Manual

6
2. ELECTRICAL SAFETY INFORMATION:
2.1 Electrical equipment including cables, cords and plug connections must
not be defective. Please check before using.
2.2 Do not plug the Generator directly into a wall socket outlet.
2.3 The Generator must not be connected to other power sources such as
the power company supply mains. In special cases where stand-by
connection to existing electrical systems or integration therewith is
intended, note that it is a legal requirement that such connection or
integration may only be performed by a competent person.
2.4 Protection against electrical shock depends on circuit-breakers that are
specially matched to the Generator. If a circuit breaker requires
replacement, it shall be replaced by a circuit breaker that has identical
ratings and performance characteristics.
2.5 Due to high mechanical stresses only tough rubber-sheathed flexible
cable should be used
2.6 If the Generator is of Class II construction, then earthing of the
Generator is not required.
2.7 Extension Cords:
When an extension cord set is connected to the generating set the
following should be considered:
2.7.1 A 1mm2 flexible cable can draw a maximum of 10A provided that
the cable is no longer than 25m.