Product Manual

24
If the generator is not grounded through your building’s system,
follow the procedure below. This procedure can only be carried
out by a licensed electrician.
1. Drive a ¾” or 1” copper pipe or rod into the ground close
to the generator. The pipe/rod must penetrate moist earth
the depth required will be dictated by local soil
conditions.
2. Connect an approved ground clamp to the pipe.
3. Run a 10-gauge wire from the clamp to the generator
grounding post located on the rear of the generator head.
4. Do not connect the generator grounding post to a water
pipe or a ground used by the radio system.