Instruction Manual

G9000 Installation and Operation Manual 17
TABLE 1.5.a Detail of Specifications
Rated Output kVA
80
100
160
225
Rated Output kW
72
90
144
202.5
AC INPUT
Configuration
3 phase, 3 wire
Voltage
480 V +15% to -20%
Frequency
60 Hz +/-10%
Power Factor
>.99 Lagging at 25% - 115% Load
Reflected Current
THD
3% max. at 60% - 100% load (no input filter required)
6% max. at 25% - 59% load.
STATIC BYPASS INPUT
Configuration
3 phase, 3 wire
Voltage
480 V +/-10%
Frequency
60 Hz +/-5%
BATTERY
Type
Lead Acid
Ride Through
Application Specific
Nominal Voltage
480 Vdc
Minimum Voltage
400 Vdc
DC Ripple
0.23%
0.23%
0.23%
0.29%
DC Charging Current
20 Adc
25 Adc
40 Adc
56 Adc
Number of Cells
240
AC OUTPUT
Configuration
3 phase, 3 wire
Voltage
480 V
Voltage Regulation
+/-1%
Frequency
60 Hz
Frequency
Regulation
+/-0.01% in free running mode
Power Factor
0.9 nominal
Power Factor Range
0.9 lagging to 0.95 leading (within output kW rating)
Voltage THD
2% maximum THD at 100% Linear Load
5% maximum THD at 100% non-linear load
Transient Response
+/-2% maximum at 100% load step
+/-1% maximum at loss/return of AC power
+/-5% maximum at load transfer to/from static bypass
Transient Settling
(Recovery) Time
Less than 20ms
Voltage Unbalance
1% maximum at 100% unbalanced load