Owner manual

3
1600EP Series Instruction Manual Addendum
UPS Speci cations
STANDARD MODELS: 3.6 kVA-C1; 3.6 kVA; 6 kVA; 8 kVA
Unit (Capacity)
3.6 kVA-C1
(3.1 kW)
1
3.6 kVA (3.1 kW)
1
6 kVA (5.1 kW)
1
8 kVA (6.8 kW)
1
General
Topology True On-line
Certi cations UL, CUL, ISO 9001, NEMA/PE1-1993
Input Characteristics
Input Voltage Single-phase, 208/240 Vac, -30% – +10%
Input Frequency 45 – 65 Hz (auto-sensing)
Input Capacity 3.6 kVA 6.0 kVA 8.0 kVA
Input Power Factor > 0.95 for all loads
Current THD (linear load) < 5% total harmonic distortion
Included AC Input Breaker
Rating
30 A/277 V 50 A/277 V 60 A/277 V
Battery Characteristics
Battery Type Valve Regulated Lead Acid, Flame Retardant
Backup time, fully charged
@ 0.7 power factor, 77 °F
8 min.
minimum
2
14 min.
minimum
2
7 min.
minimum
2
Backup time, fully charged
@ 0.85 power factor, 77 °F
7 min.
minimum
2
10 min.
minimum
2
7 min.
minimum
2
Recharge Time 24 hr. (full), 12 hr. (90%) for internal batteries only
3
Battery Voltage (Nominal) 144 Vdc 216 Vdc 216 Vdc 288 Vdc
Output Characteristics
Output Voltage Single-phase, 240/208/120 V
Output Voltage Regulation ± 3%
Output Frequency ±0.5 Hz/1 Hz/1.5 Hz (factory or authorized service center selectable only)
AUTO/MAN Frequency Factory or authorized service center selectable only
Voltage THD < 3% for linear load; < 6% for non-linear load
Common-Mode Noise < 0.5Vrms
Rated Load Power Factor 0.85 (0.6 – 1.0) lagging
Ef ciency (ac-dc-ac) > than 83% (without battery charge)
Voltage Transient < ±8% (Load of 0 – 100 %)
Rated Output Current (rms) 15 A 25 A 33.3 A
Max. Peak Output Current 45 A 75 A 100 A
Inverter Overload Capacity 125% for 30 sec./150% for 10 sec.
Bypass Overload Capacity 125% for 10 min./1000% for 1 cycle