Owner manual

2
1600EP Series Instruction Manual Addendum
Introduction
This addendum to the 1600EP Series User Manual adds information to the existing Speci cation sheet
that is speci c to the 3.6kVA-C1 (UE36L036C61TC1) UPS.
Purpose and Scope
This addendum to the 1600EP Series User Manual adds the speci cations for the 3.6kVA-C1
(UE36L036C61TC1) UPS to the existing Speci cation sheet.
The information in this addendum is to be used in conjunction with the Safety, Installation, and
Operation information provided in the 1600EP Series Instruction Manual (55288-001).
Speci cations for the 3.6 kVA-C1 UPS
Battery Low Voltage Tolerances
UPS Capacity 3.6 kVA-C1
Nominal Voltage (V
NOM
) 144 VDC
Alarm Voltage (V
LOW
) 130 VDC
Shutdown Voltage (V
MIN
) 114 VDC
Rated Battery Voltage
Model V
MAX
V
MIN
I
CHARGE
3.6 kVA-C1 163 114 1.0 A
Dimensions (ref. 1600EP Instruction Manual, “External Layout,” pg. 53)
Model A (Height) B (Width) C (Length) D (Body
height)
E (Unit oor
clearance)
3.6 kVA-C1 21 in.
(533 mm)
10 in.
(2554 mm)
33 in.
(838 mm)
18.2 in.
(462 mm)
2.8 in.
(72 mm)
Shipping Weight
Model Pounds Kilograms
3.6 kVA-C1 325 147