User Manual
Options
>
Remote monitoring and
diagnostics via
LAN or internet
>
UPS management software
facilitates operation and
maintenance of the
UPS
>
Input and output
PDU available
for 5-10k
VA sizes
>
Three available slots for options:
•
SNMP plug-in card, potential-
free relay contacts
•
RPA
™
Kit: Any single UPS can
be easily field-configured for
Redundant Parallel Architecture
™
• RS-232/contact interface,
providing maximum flexibility
>
Dual
AC input option
>
Additional external matching
battery cabinets are available for
extended runtime requirements
(Contact the factory for details)
Technical Specifications – UL approved
Height Width Depth
Enclosure A 26.8" (68 cm) 12.3" (31.2 cm) 28.7" (72.9 cm)
Enclosure B 39.2" (99.6 cm) 12.3" (31.2 cm) 28.7" (72.9 cm)
Table 1
Models
LP-11U - 5 LP-11U - 5 LP-11U - 6 LP-11U - 6 LP-11U - 8 LP-11U - 10
(120V) (120V)
Rating (VA/W) 5000 / 4000 5000 / 4000 6000 / 4800 6000 / 4800 8000 / 6400 10,000 / 8000
Backup Time @ 50% / 100% loads 25 / 10 min. 25 / 10 min. 20 / 8 min. 20 / 8 min. 29 / 11 min. 22 / 8 min.
Enclosure (Table 1) A BABAA
Net Wgt Incl. Batteries (kg/lbs) 134 / 295 175 / 386 134 / 295 175 / 386 175 / 386 186 / 410
Input Voltage (
VAC)
Nominal (V) 208 120 208 120 208 208
Range @ 100% Load (V) 162-285 81-141 162-285 81-141 162-285 162-285
Range @ 50% Load (V) 146-285 72-141 146-285 72-141 146-285 146-285
Input Power Factor .99
Input Frequency (Hz) 40-70
Output Power Factor .8
Output Voltage (
VAC) (sinusoidal) 120+208+220/230/240 User Selectable
Output Frequency (Hz) 50 / 60 (Selectable)
Output Voltage Regulation +/- 1%
Output
THD at Linear Load < 1%
Output
THD at Non-linear Load < 2%
Crest Factor Handling Capacity of a Non-linear Load 5:1
Overload Capability on Inverter 110% 20 min., 130% 3.5 min., 150% 2 min.
Color Front bezel: Aluminum Grey (RAL 9006); Cabinet: White (RAL 9003)
Environment Protection IP20 (IEC 60529 &
DIN 40050)
Operating Temperature / Humidity –
UPS 14° F - 104° F (-10° C - 40° C) / 95% Non-condensing
Audible Noise 40-50 dBA - 3.3 feet (1 meter)
Safety Classifications & Listings UL, cUL 1778; EN50091-1-1; EN 60950;
IEC 62040-1
EMI FCC Part 15 Class A / EN50091-2,
IEC/EN 62040-2 Class A
Surge Protection IEC 61000-4-5 (6kV 1.2/50 μsec – 3kA 8/20 μsec) IEEE 587 B, EN 50091-2
Connectivity RS-232; programmable alarm contacts (optional); SNMP (optional)
Warranty 24 months after seller’s shipment to customer *
* Extended Warranties available
Represented by:
GE Digital Energy –
Power Quality
701 E 22nd Street
Lombard, IL 60148
USA
800 637 1738
www.gedigitalenergy.com/ups
Information subject to change
without notice. Please verify
all details with
GE.
© 2009 General Electric Company
All Rights Reserved
GEA-D2003 (9/09)
U.S.-Based