Instruction Manual
Gamatronic Electronic Industries Ltd.
POWER
+
SA User Guide (UL), Release 1.0
88
21. POWER+ SA SPECIFICATIONS
POWER+ SA UPS 3X208V+N 2X120V+N
Topology True on-line battery, double conversion
Model 10kVA
Input
Voltage (V)
3x208V+N 2x120V+N
Voltage range (%) – 27% and + 20%
Current 28A max. per phase, no inrush current at startup
Frequency 47— 63Hz
Power walk-in (sec) > 60
Power factor 0.99
THDI (%) 5
Output
Rated power 10kVA / 8kW 7.5kVA / 6kW
Frequency tracking range 60Hz ±1, ±2, ±3 (selectable)
Slew rate 1 Hz/sec
Voltage (V)
3x208V+N 2x120V+N
Static regulation % ±1
Regulation for unbalanced load % ±1 for 100% unbalanced load
Dynamic response to 100% load step (%) 2
Overload 110% : 10 minutes; 125% : 60 seconds; 1000% : 1 cycle
Waveform Sinusoidal
THD (%) Less than 2 for linear load
Load CF 6:1
DC/AC efficiency (nominal) 96%
AC/AC efficiency (nominal) 94%
Static Switch
Input connection Dual input
General
Maximum power dissipation (Po=8KW) 510W (1740 BTU) 384W (1310 BTU)
Ambient temperature (°C)
-10 to +40 (operating)
-20 to +60 (storage)
Relative humidity (%) 95 max., non-condensing
Altitude (m) 1500 without derating
Enclosure IP20
Cooling system Multi-fan with speed control (forced)
Acoustic noise (full load) at 1.5m 51dBA
MTBF (hrs) 250,000
Dimensions (H x W x D, cm.) 56 x 9 x 60
Weight 18kg
LCD display
Input Voltage, current, frequency
Output Voltage, current, frequency
Batteries Voltage
Log (events memory) Last 200 events
Communication
RS232 port, Yes
Alarm and shutdown monitor Yes
SNMP link (optional) Option
Standards
EMC emissions IEC 62040-2; FCC part 15/B
Safety UL1778; IEC 62040-1-1
Design IEC 62040-3
Low magnetic field radiation EMF as per ICNIRP
Batteries
Type Sealed, valve-regulated, lead-acid
Number 32x7Ah
Voltage 12V
Backup time (min.) 6 at 50% load
Recharge time (hrs.) Appx. 1-2
Battery cabinet
Dimensions (H x W x D, in cm) 45 x 26 x 60
Weight (kg) 90
All specifications subject to change without notice.