User Manual
Gamatronic Electronic Industries Ltd.
POWER
+
RM100,
3X208 V, User Guide, Release 2.7ys
59
6.2 POWER
+
Shutdown (Switching to Bypass)
1. Switch the load OFF.
2. Press twice on the On/Off button.
3. Wait 2 minutes for the POWER
+
to shut down. The control screen will indicate UPS
OK (OFF).
LOAD LEVEL ---22:21:18---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW OK (BYP)
Figure 70: Main screen – switching to bypass
Note: This does NOT switch the entire POWER
+
OFF. Power is still delivered to the load but in
bypass.
Figure 71: Bypass indication
6.3 POWER
+
Total Shutdown (No Ac Output)
4. Switch the load OFF.
5. Press and hold the On/Off button for 10 seconds.
6. The control screen will indicate UPS OK (OFF).
LOAD LEVEL ---23:14:40---
L1:__________ 000A, 120V BATTERY: 432V
L2:__________ 000A, 120V UPS OK (OFF)
L3:__________ 000A, 120V STSW Warning !
Figure 72: Main screen – total shutdown