User Manual

Gamatronic Electronic Industries Ltd.
POWER
+
RM100,
3X208 V, User Guide, Release 2.7ys
165
16. TECHNICAL SPECIFICATIONS
Table 25: Technical specifications for the RM100 3x208 Vac
POWER
+
TECHNICAL DATA
Topology True On-line Battery, Double Conversion, VFI
Construction Modular parallel hot-plugged modules
Operation Continuous
Input
Voltage
3 × 208 Vac + N (3 x 120 Vac, N = Neutral)
Voltage range +15 % and -25 %
Current 28 A per module – no inrush current at startup
Frequency 47 Hz–63 Hz
Power walk-in > 60 sec.
Power Factor 0.99
THDI 5 %
Output
Rated power for 3-3 configuration: 10 kVA / 8 kW to 100 kVA / 80 kW
Frequency tracking range ±2 Hz
Slew rate 1 Hz / sec.
Voltage 3 × 208 Vac + N (3 x 120 Vac, N = Neutral)
Static Regulation ±1 %
Regulation for unbalanced load ±1 % for 100% unbalanced load
Dynamic resp. to 100% load step ±2 %
Overload 110 % for 10 min., 125 % for 60 sec., 1000 % for 1 cycle
Waveform Sinusoidal
THD Less than 2 % for linear load
Load CF 4:1
Ac-Ac efficiency (nominal) Up to 94 % at full load
Dc-Ac efficiency (nominal) Up to 97 % at full load
Batteries
Dc-Link Voltage ±160 to ±216 Vdc
Quantity (in optional external cabinet) 2 x 32 x 12 Vdc (40 Ah)
Type Sealed, lead acid, rechargeable
General
Maximum power dissipation (Po=8 kW) N*510 W (N*998 BTU), where N = # modules
Ambient temperature
operation (up to 80 kVA):
operation (90 and 100 kVA)
storage:
+14 to +104 °F (-10 to +40 °C)
+14 to +86 °F (-10 to +30 °C)
-4 to +140 °F (-20 to +60 °C)
Relative humidity 95 % max., non-condensing
Altitude 1500 m without derating
Enclosure IP20
Cooling system Multi-Fan with speed control (forced)
Standards
EMC
IEC 62040-2, under EMC 2004/108/EC
Design
IEC 62040-3
Safety
IEC 62040-1, under LVD 2006/95/EC
Low magnetic field radiation
EMF as per ICNIRP
All specifications are subject to change without notice.