User Manual

Gamatronic Electronic Industries Ltd.
POWER
+
RM100,
3X208 V, User Guide, Release 2.7ys
87
3. Use the arrow keys to set BATEND and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATEND]
FLOATING CHARGE SETUP
VOLTAGE SETTING: 170.0V
Figure 131: Set BATEND
4. Select BATLOW:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI SELECT ITEM:1
Figure 132: Battery floating charge alarm setup menu
5. Use the arrow keys to set BATLOW and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BATLOW]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 170.0V
Figure 133: Set BATLOW
6. Select BAT-HI:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT]
1> BATEND
2> BATLOW
3> ------
4> BAT-HI SELECT ITEM:1
Figure 134: Battery floating charge alarm setup menu