Owner manual

Gamatronic Electronic Industries Ltd.
POWER
+
RM
50 KVA, N.Am. Std. – User Guide, Release 1.9
83
8.4 “Self-test” Option
You can run a self-test at any time without interfering in the normal operation of the POWER
+
. A
self-test is also initiated by the POWER
+
itself each day at midnight.
Figure 115: Main Menu option 3 (“Self Test”)
The failure of a self-test sets on the self-test alarm. The self-test alarm can only be cleared by a
subsequent successful self test, or it can be cleared manually by a maintenance technician.
Powering the POWER
+
down and up, for example, does not clear the self-test alarm. This is
because the failure of a self-test is considered a serious event that should not be “forgotten”. A
self-test failure is also recorded in the alarm log.
[Main Menu > SELFTEST]
Wait for results…
STATIC RAM: PASSED R.T CLOCK: PASSED
EEPROM – 1: PASSED
EEPROM – 3: PASSED DC SUPPLIES: PASSED
Figure 116: Result screen from self-test