Owner manual
Gamatronic Electronic Industries Ltd.
POWER
+
RM
50 KVA, N.Am. Std. – User Guide, Release 1.9
79
6. View the system jumper settings without remote panel:
[Main Menu > SYSTEM > ▼ ▼ ▼]
JMP: JMP1, JMP2, JMP3, JMP6 and JMP9
=IN 1. NOT HARD SILICON
2. SILICON MODE 6. NO RMT PAN.
12369 3. CAPACITY LOW 9. AC: 120V
Figure 104: Jumper settings WITHOUT remote panel
7. View the system jumper settings with remote panel:
[Main Menu > SYSTEM > ▼ ▼ ▼]
JMP: JMP1, JMP2, JMP3, JMP6 and JMP9
=IN 1. NOT HARD SILICON
2. SILICON MODE 6. Remote pan.
12369 3. CAPACITY LOW 9. AC: 120V
Figure 105: Jumper settings WITH remote panel
Note: In Figure 104 and Figure 105, “Silicon mode” indicates that the configuration jumper is
installed, thus allowing for m
odifications. “Hard Silicon”
indicates that the factory defaults
hard reset jumper is installed. This is required only at the factory or whenever software
reset fails. Refer to section 8.15.9.3 for a detailed description of jumpers.
8. View the internal controller voltages:
[Main Menu > SYSTEM > ▼ ▼ ▼ ▼]
5VDC : 5.19V CONTROLLER INTERNAL
12VDC: 12.01V VOLTAGES
5VP : GOOD
5V2 : GOOD -12VDC: GOOD
Figure 106: Internal controller voltages
9. View battery parameters:
[Main Menu > SYSTEM > ▼ ▼ ▼ ▼ ▼]
BATTERY CHARGE LEVEL: 010Ah 050%
WHILE TOTAL CAPACITY: 020Ah
REMAINING BACKUP: 0010 MINUTES
BATTERY TEMPERATURE: 12
°C
Figure 107: Battery parameters