Owner manual

Gamatronic Electronic Industries Ltd.
POWER
+
RM
50 KVA, N.Am. Std. – User Guide, Release 1.9
97
7. Use the arrow keys to set BAT-HI, press Ent, and then Esc:
[Main Menu > SETUP > (password) > ALARM SET > FLOAT VOLT > BAT-HI]
FLOATING CHARGE ALARM SETUP
VOLTAGE SETTING: 340.0V
Figure 146: Set BAT-HI
8.8.3 Setting Battery Over/Under Temperature Alarms
1. Select TEMPERATURE:
[Main Menu > SETUP > (password) > ALARM SET]
1> AC VOLT 5> --------- 9>INTEGRAT.
2> FLOAT VOLT 6> ---------
3> --------- 7> TEMPERATURE
4> --------- 8> ---------
Figure 147: Alarm set menu
2. Select OVER TEMPERATURE:
[Main Menu > SETUP > (password) > ALARM SET > Temperature]
1> OVER TEMPERATURE
2> UNDER TEMPERATURE
PLEASE SELECT
Figure 148: Over/Under temperature menu
3. Use the arrow keys to set the battery maximum temperature alarm value and press Ent:
[Main Menu > SETUP > (password) > ALARM SET > Temperature > OVER TEMPERATURE]
SET OVER TEMPERATURE ALARM VALUE
( 2 – 99) DEGREES
45
Figure 149: Set battery maximum temperature alarm