Table 13: Log Messages
# Message Explanation
01
UPSMAJ More than 1 UPS Module is sending an alarm or fault warning
02
UPSMIN Single UPS Module is sending an alarm or fault warning
03
------ N.A.
04
------ N.A.
05
LOADBP Load is now running on bypass. See Table 14 on page 87 to interpret
the LOADBP value.
06
VIBRA_ Alarm(s) vibrating. Alarm is frequently raised and lowered. Ignore to
avoid loading the log filling up.
07
OVTEMP Excess temperature
08
OUTFLT No AC output to load
09
BAT-HI Excessive battery voltage
10
------ N.A.
11
BATEND End of battery backup. Battery is discharged to shutdown limit
12
BATLOW Low battery voltage
13
STSWRN Static Switch Warning or alarm
14
E.P.O. Emergency Power Off is active
15
EQ-HST Battery is currently charging in equalizing mode, dc voltage is
temporarily increased
16 BATFLT Batteries failed last test
17 USER-1 User 1 input open
18 USER-2 User 2 input open
19 USER-3 User 3 input open
20 AC-BRN Input AC supply Brown Out
21 ACIN_H AC input excessive
22 ACFAIL AC input failure
23 STSWCM Static Switch does not respond
24 SLFFLT Last controller self-test failed
25 BAT-CB Battery Circuit Breaker Open
26 CURSHR Current Sharing fault, load current is not equally divided between
modules
27 UPSOUT Fault (no current) in 1 or more output stage
28 UPSHDN UPS shutdown by EPO, Battery Discharge, ON/OFF pressed