Specifications
Control Valves - SMARTLINK
®
MRV
www.maxoncorp.com
combustion systems for industry
Maxon reserves the right to alter specifications and data without prior notice.
© 2014 Copyright Maxon Corporation. All rights reserved.
10-30.7-88
E - i - 3/14
50120624-001/
Position
Index
Light
# On
Position
Command
(%)
Position
Command
(mA)
Valve-2 Valve-3
Position
(deg. or mA)
Burner Pressure
or Flow
Position
(deg. or mA)
Burner Pressure
or Flow
0 0 00.00% 4.000
0.5 0, 1 05.56% 4.889
1 1 11.11% 5.778
1.5 1, 2 16.67% 6.667
2 2 22.22% 7.556
2.5 2, 3 27.78% 8.444
3 3 33.33% 9.333
3.5 3, 4 38.89% 10.222
4 4 44.44% 11.111
4.5 4,5 50.00% 12.000
5 5 55.56% 12.889
5.5 5, 6 61.11% 13.778
6 6 66.67% 14.667
6.5 6, 7 72.22% 15.556
7 7 77.78% 16.444
7.5 7, 8 83.33% 17.333
8 8 88.89% 18.222
8.5 8, 9 94.44% 19.111
9 9 100.00% 20.000
9.5 9, 0 Standby No inputs
10 9, 0, 1 Purge PPC On
10.5 9, 1 Lightoff LPC On