Table 9: SMARTLINK
®
MRV User Display Terminal Descriptions and Wiring Specifications
Table 9: SMARTLINK
®
MRV User Display Terminal Descriptions and Wiring Specifications
Terminal Name (Label Abbreviation) Description
Network Interface Terminals
(4-position screw-type connector)
Field 24VDC Power (F24+)
Field 24VDC Common (F24-)
Data A (DA)
Data B (DB)
Communications network and field +24VDC power
1000 feet maximum to optional remote User Display
EIA Level 4 cable, 2 twisted pair with shield, 22 AWG
Cable sources:
MAXON P/N 1055654 (100 ft. length); P/N 59829 (500 ft. length)
Connect-Air International P/N W22P-1005
Suggested wiring color code convention:
Orange/White (F24+), Orange (F24-), Blue (DA), Blue/White (DB)
Note on shield wire terminations:
The shield wire should be connected to the actuator "SHD" terminal (keeping the shield length to 1 inch or less). In addi-
tion, the shield wire should be tied to ground as it enters the enclosure of the Control Interface (keeping the maximum
length to 2 inches or less).
Relay Drive Output Terminals
(2-position screw-type connector)
Open Collector +(OC+)
Open Collector - (OC -)
OC+ and OC- are for future use
30VDC, 100 mA (max)
14-22 AWG wire
No length restrictions other than voltage drop considerations
Follow all local required wiring codes