Specifications

Control Valves - SMARTLINK
®
MRV
www.maxoncorp.com
combustion systems for industry
Maxon reserves the right to alter specifications and data without prior notice.
© 2014 Copyright Maxon Corporation. All rights reserved.
10-30.7-76
E - i - 3/14
50120624-001/
Table 8: SMARTLINK
®
MRV Network Interface Terminal Descriptions and Wiring Specifica-
tions
Table 8: SMARTLINK
®
MRV Network Interface Terminal Descriptions and Wiring Specifications
Terminal Name Description
Network Interface Terminal Connectors
(4-position plug-type; Quantity-8)
100 feet maximum length to each actuator; 1000 feet maximum to optional remote User Display
EIA Level 4 cable, 2 twisted pair with shield, 22 AWG
Cable sources:
MAXON - P/N 1055654 (100 ft. length); P/N 59829 (500 ft. length)
Connect-Air International P/N W22P-1005
Suggested wiring color code convention:
Orange/White (F24+), Orange (F24-), Blue (DA), Blue/White (DB)
300 feet maximum length to each actuator with Belden P/N 3086A: 2 twisted pair with shield;
16 AWG - power pair, 20 AWG - data pair
Suggested wiring color code convention: Brown (F24), Blue (FCOM), White (DA), Black (DB)
Note on shield wire terminations:
The shield wire of each actuator network cable should be connected to the actuator "SHD" terminal (keeping the shield
length to 1 inch or less). In addition, the shield wire should be tied to ground as it enters the enclosure of the Control
Interface (keeping the maximum length to 2 inches or less).
Valve-0:
Field 24VDC Power (F24+)
Field 24VDC Common (F24-)
Data A (DA)
Data B (DB)
Output: Valve #0 communications network and field +24VDC power
Valve-1:
Field 24VDC Power (F24+)
Field 24VDC Common (F24-)
Data A (DA)
Data B (DB)
Output: Valve #1 communications network and field +24VDC power
Valve-2:
Field 24VDC Power (F24+)
Field 24VDC Common (F24-)
Data A (DA)
Data B (DB)
Output: Valve #2 communications network and field +24VDC power
Valve-3:
Field 24VDC Power (F24+)
Field 24VDC Common (F24-)
Data A (DA)
Data B (DB)
Output: Valve #3 communications network and field +24VDC power
User Display:
Field 24VDC Power (F24+)
Field 24VDC Common (F24-)
Data A (DA)
Data B (DB)
Output: User Display communications network and field +24VDC power
Note: Factory-wired in MRV 24"x20" Interface Panel
SL-MRV-CI:
Field 24VDC Power (F24+)
Field 24VDC Common (F24-)
Data A (DA)
Data B (DB)
Input: Communications network and field +24VDC power from SMARTLINK
®
MRV Control Interface
Note: Factory wired in MRV Interface Panel
Spares (2):
Field 24VDC Power (F24+)
Field 24VDC Common (F24-)
Data A (DA)
Data B (DB)
Output: Spare communications network and field +24VDC power for optional remote User Display and future SMART-
LINK
®