Specifications
Control Valves - SMARTLINK
®
MRV
www.maxoncorp.com
combustion systems for industry
Maxon reserves the right to alter specifications and data without prior notice.
© 2014 Copyright Maxon Corporation. All rights reserved.
10-30.7-69
E-i -3/14
50120624-001/
SMARTLINK
®
Reference Tables
Table 1: SMARTLINK
®
MRV Interface Panel Terminal Descriptions
Table 1: SMARTLINK
®
MRV Interface Panel Terminal Descriptions
Terminal Designator:
Name (Label Abbreviation)
Description
Line Voltage Terminals Location: Terminal block assembly on lower DIN-rail of Interface Panel
Line Voltage (L1)
100 to 230 VAC customer power source, 50-60 Hz
2 Valve System: 61 Watts (max) load
3 Valve System: 90 Watts (max) load
4 Valve System: 118 Watts (max) load
Line Voltage Switched (L1S)
Switched line voltage from breaker used to locally power down the SMARTLINK
®
MRV System.
Note: No field wires should be connected to these terminals.
Neutral (L2) Neutral
Protective Earth (PE) Earth Ground
Relay Output Terminal Block
Location: Terminal block assembly on lower DIN-rail of Interface Panel
All relay outputs below are Form A (Normally Open) contacts with the following specifications: 12A, 250 VAC/DC
(max)
Alarm (ALM)
Alarm Return (ALMR)
Output: Alarm relay contact closes if one or more MRV alarm or fault conditions exist. (See page 10-30.7-66 for
alarm / fault descriptions.)
Control Enable (CE1)
Control Enable Return (CE1R)
Control Enable (CE2)
Control Enable Return (CE2R)
Output: Control Enable #1 & #2 relay contacts are opened when one or more SMARTLINK
®
MRV "fault" conditions
occur; both contacts are closed when no system fault exists. A SMARTLINK
®
MRV "alarm" condition does not affect
the state of these contacts. (See page 10-30.7-66 for descriptions of fault conditions and page 10-30.7-50 for wiring
the Control Enable in a typical combustion system.) The two contacts are wired in series to prevent a single-point,
welded contact failure. Both CE1 and CE2 interface relays are driven by Control Interface output, RO2.
Note: A jumper is installed between CE1R and CE2. Field wiring should be connected to only CE1 and CE2R.
WARNING: Proper wiring of these contacts to the burner management equipment is an essential safety requirement
for burner shut down in the event of a SMARTLINK
®
MRV failure.
Purge Position Proven (PPP)
Purge Position Proven Return (PPPR)
Output: Purge Position Proven relay contact closes when all valve positions are greater than or equal to maximum
positions or user-defined, custom purge positions.
Light-Off Position Proven (LPP)
Light-Off Position Proven Return (LPPR
Output: Light-off Position Proven relay contact closes when all valve positions are less than or equal to minimum posi-
tions or user-defined, custom light-off positions
Custom Output #1 (CO1)
Custom Output #1 Return (CO1R)
Output: For systems with software version release 1C or later, the CO1/CO1R relay contact is opened when one or
more SMARTLINK
®
MRV "fault" conditions occur; this contact is closed when no system fault exists and serves as a
fail-safe, redundant combustion permissive/interlock output. (See page 10-30.7-66 for descriptions of all fault condi-
tions and page 10-30.7-50 for wiring CO1/CO1R in a typical combustion system.) The CO1 interface relay is ener-
gized by Control Interface output RO5. The CO1/CO1R contact opens 6 seconds after the Control Enable contacts
are opened. A SMARTLINK
®
MRV "alarm" condition does not affect the state of this contact.
WARNING: Proper wiring of this relay contact to the burner management equipment is an essential safety require-
ment for burner shut down in the event of a SMARTLINK
®
MRV failure.
Relay Input Terminal Block
Location: Terminal block assembly on lower DIN-rail of Interface Panel
All relay inputs below are solid-state with following specifications:
Input On-State Voltage: 120VAC (230VAC and 24VDC options available)
Input On-State Current: 25 mA (max)
Input Off-State (Leakage) Current: 4 mA
Command Common (CCOM) N/A: Common for all solid-stage relay input command signals listed below.
Purge Position Command (PPC)
Input: Purge Position Command drives all SMARTLINK
®
MRV valves to their maximum or user-defined, custom purge
positions if the LPC and MVC inputs are not energized.
Light-off Position Command (LPC)
Input: Light-off Position Command drives all SMARTLINK
®
MRV valves to their minimum or user-defined, custom
light-off positions if the MVC input is not energized.
Modulate Valves Command (MVC)
Input: Modulate Valves Command enables all SMARTLINK
®
MRV valves to synchronously modulate based on the 4-
20 mA firing rate command input signal. This command overrides the PPC and LPC commands when energized.
Remote Reset Command (RRC)
Input: Remote Reset Command resets the MRV system when a fault condition occurs and the system has entered
Shutdown Mode. (See page 10-30.7-66 for fault condition descriptions.)
Custom Application Command #1 (CAC1) Input: Reserved for future use.
Custom Application Command #2 (CAC2) Input: Reserved for future use.
4-20 mA Terminal Block Location: Terminal block assembly on lower DIN-rail of Interface Panel
4-20 mA In A + (INA+)
Input: Isolated 4-20 mA firing rate command; current flows into INA+ and out of INA- terminal; 4 mA = 0% firing rate
demand (minimum valve positions); 20 mA = 100% firing rate demand (maximum valve positions)
4-20 mA In A- (INA-)
4-20 mA In B+ (INB+)
Input: Reserved for future use.
4-20 mA In B- (INB-)