Specifications
Control Valves - SMARTLINK
®
MRV
www.maxoncorp.com
combustion systems for industry
Maxon reserves the right to alter specifications and data without prior notice.
© 2014 Copyright Maxon Corporation. All rights reserved.
10-30.7-60
E - i - 3/14
50120624-001/
System Configuration
There are 7 SMARTLINK
®
configuration settings that can be changed through execution of the commands listed below. Detailed
explanations of each setting appear in Reference Table 11: SMARTLINK
®
MRV System Configuration Summary (page 10-30.7-
79).
Command Name Command Number Factory Default
Select Loss of Signal (LOS) Position B-0 Setting #0: Position Index 0 (Minimum)
Select Control Deadband B-3 Setting #2: 0.06% Deadband
Select Startup Configuration B-4 Setting #0: Default Startup
Select Auto Ramp Adjust B-6 Setting #1: Auto Ramp ON
Select Movement Configuration B-7 Setting #1: Medium Speed (~40 seconds)
Enter New Lock Passcode C-4 Default Passcode: 0, 0, 0, 0
Select Lock Enable/Disable C-5 Setting # 0: Lock Disable
Review the factory default settings before changing any of the system configuration settings. In many applications, modification of
the default settings is not necessary. If a setting does need to be changed, follow the procedure below.
Procedure for Changing a System Configuration Setting:
a) Select and enter the required system configuration command.
b) After the command is entered, one of the numbered (0-9) lights will be on, indicating the current configuration setting. (For
example: If the lock configuration is set to #0, Lock Disable, the 0 light will be solidly lit after Command C-5, Lock Enable/
Disable, is entered successfully.)
c) Select the desired configuration setting by using the INC/DEC switch. As the INC/DEC switch is momentarily pushed up or
down, the selected setting changes as indicated by turning on the corresponding numbered (0-9) light.
d) Push the ENTER button after the desired configuration setting is selected. The numbered light (i.e. selected configuration)
that is lit will momentarily turn off indicating the command is complete and the configuration setting is saved.
e) To confirm the correct setting is saved, re-enter the command and verify the new setting by the numbered (0-9) light indication.