Specifications
Control Valves - SMARTLINK
®
MRV
www.maxoncorp.com
combustion systems for industry
Maxon reserves the right to alter specifications and data without prior notice.
© 2014 Copyright Maxon Corporation. All rights reserved.
10-30.7-54
E - i - 3/14
50120624-001/
NOTES:
NOTE 1: Recommended wire color code for SMARTLINK
®
MRV Control Network
NOTE 2: All shields should terminate to GND within 6" of where it enters the cabinet.
NOTE 3: Blue 14AWG MTW/AWM wire is to be used on 4-20 mA signal.
NOTE 4: Type "J" thermocouples are color coded with white as (+) and red as (-). Type "K" thermocouples are color coded with yellow as (+) and
red as (-). Thermocouple wires must be run in separate conduit.
NOTE 5: Installation, operation, and maintenance shall conform with local standards, national and local codes, and authorities having jurisdiction.
NOTE 6: Wire numbers assigned only to SMARTLINK
®
MRV Interface Panel.
NOTE 7: Symbol Key
NOTE 8: The ground reference for all input command signals must be wired by the customer and its termination depends on the relay input
interface purchased (i.e. VAC vs. VDC).
NOTE 9: WARNING: Relay contacts CE1/CE2R (and CO1/CO1R for systems with software version release 1C or later) must be wired in series
with the burner management permissive/interlock circuit to ensure the burner can be shut down in the event of a SMARTLINK
®
MRV
failure. If the SMARTLINK
®
MRV system is purchased without a MAXON Relay Output Interface (ROI), the commissioning engineer is
responsible for verifying that appropriate interface relays are wired to the burner management system and Control Interface relay drive
outputs, RO2 (and RO5 for systems with software version release 1C or later).
NOTE 10: This wiring schematic represents electrical connections in a "typical" product application. Please refer to the schematics of the specific
application for troubleshooting.
Component
Terminal
Designation
SMARTLINK
®
MRV Network Cable
MAXON
(not to exceed 100 ft.)
Belden
(not to exceed 300 ft.)
F24+ / +24 white / orange brown
F24- / GND orange blue
DA white / blue white
DB blue black
Indicates terminals and wiring in SMARTLINK MRV control panel
Indicates component terminals
Indicates SMARTLINK MRV interface panel DIN-rail terminal block
Indicates adjacent SMARTLINK MRV interface panel DIN-rail terminal blocks jumpered together
Indicates external wiring
Maintain the integrity of the MAXON enclosure by using NEMA 4X or IP66 rated dust- and water-tight
electrical connectors. Use cable-sealing grips and strain-relief loops for any cord or cable. Use internal
sealing materials on all conduit connections. Moisture can have a harmful effect on device internals if
permitted to enter through wiring connectors. Ensure that the device connection is not at a low point of the
conduit to avoid condensation run-off into the housing; install a drip loop if necessary. Make sure that the
access cover plate is in place and securely fastened. All cover screws should be tightened using an
alternate cross-corner tightening pattern. Cover screws should be checked periodically to ensure
adequate sealing protection.