Specifications
Control Valves - SMARTLINK
®
MRV
www.maxoncorp.com
combustion systems for industry
Maxon reserves the right to alter specifications and data without prior notice.
© 2014 Copyright Maxon Corporation. All rights reserved.
10-30.7-44
E - i - 3/14
50120624-001/
SMARTLINK
®
MRV Components
As shown below, the minimum SMARTLINK
®
MRV system requires two Valve Actuators and one (DIN rail-mounted) Control
Interface. A total of four Valve Actuators can by supported by one Control Interface. In addition, several optional DIN rail-mounted
components are available to simplify electrical interfacing and commissioning. These optional components include:
a) Relay Input Interface – Provides the electrical interface between the 6 Control Interface inputs and the customer’s burner
management or flame safety device. This device is available in 120VAC, 230VAC, and 24VDC models.
b) Relay Output Interface – Provides the electrical interface between the 5 Control Interface outputs and the customer’s burner
management or flame safety device.
c) Network Interface – Provides a plug-type terminal connector for all SMARTLINK
®
MRV field devices.
d) User Display – Provides a 4-line x 20-character LCD display for system commissioning and maintenance.
e) Universal Power Supply – Provides regulated 24VDC power to all SMARTLINK
®
MRV system components.
These optional components can be ordered individually and wired by the customer. However, two SMARTLINK
®
MRV Interface
Panel assemblies are available with factory-wired components as follows:
(1) 24” x 20” Interface Panel: Includes factory-wired Input & Output Relay Interfaces, Network Interface, Supply, Control
Interface, User Display, and Terminal Block Assembly
(2) 20” x 16” Interface Panel: Includes factory-wired Input & Output Relay Interfaces, Network Interface, Supply, Control
Interface, and Terminal Block Assembly
The larger, 24” x 20” Interface Panel includes a User Display. Both Interface Panels provide a 4-Amp breaker and power switch as
well as a labeled terminal block for field wiring.
The Interface Panels can be specified with a windowed, NEMA 4X enclosure in painted steel, 304-stainless or 316-stainless.
When provided with a NEMA 4X enclosure, the complete package is Class I, Division 2, and ATEX and IEC Ex approved
and no purging equipment is required.
Because SMARTLINK
®
Valve Actuators communicate digitally to the Control Interface, an EIA Level 4 Cable with 2 twisted pair
and shield is required for these connections. Required cable may be purchased from MAXON. See the Electrical Installation
section for wiring specifications.
Minimum SMARTLINK
®
MRV System Requirements
2 Valve Actuators & 1 Control Interface