User manual
Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
81
Rx Event Logs
No longer supported. Please use the Rx Update RTU Info block.
Rx Event Logs from Specific Period
Polls event logs that occurred over a specific time period from a remote RTU. It will keep polling groups of 10
logs at a time until it has received the maximum limit of logs or until the end of the event log list is reached.
RTU: (1-249) The target RTU to poll the event logs from.
Status Register: (#R or blank) When a local register is specified, the channels are defined as follows:
• Channel 1: Pending Flag. This bit is set ON when the block is activated and then set OFF after the block
has finished.
• Channel 2: Status Flag. This bit is written after the block is finished. The status flag is set OFF if the
block was successful or set ON if the block failed (communications failure).
Start Time (minutes before now), Period: A constant (0-32767) or a local register (#R). These fields are
used to specify the time period for uploading logs.
Filter Logs by: Only event logs that match the specified priority or user type are uploaded. The maximum
number of logs to upload can also be specified.