User manual

Toolbox 32 User Manual 1.47d www.cse-semaphore.com/mykingfisher
Page
49
Configuration - Pager Configuration
When paging is configured, RTU250 is automatically added to the Network List and is used for the paging
communication fail and success counters.
The RTU will send each pager message up to 3 times. Each time the pager message is transmitted, it can be
sent to the same group of pager receivers or to a different group of pager receivers. The pager message will
not be sent to the next group of pager receivers if the RTU receives an acknowledge within the configured
time.
The three groups of pager receivers to send each pager message to are called a sequence. Up to 5 different
pager sequences can be defined. When a pager message is configured in ladder logic, the paging sequence
to use must be specified. This allows different types of pager messages to be sent to different groups of
pager receivers.
A new pager message is sent to the first group of pager receivers in the sequence. If an acknowledgment is
not received by the RTU within the first acknowledge time, the pager message is then sent to the second
group of pager receivers. If an acknowledgment is not received by the RTU within the second acknowledge
time, the pager message is then sent to the third group of pager receivers. If an acknowledgment is not
received by the RTU within the third acknowledge time, the RTU will flag a communication fail for RTU250
and increment the fail counter.
Note: to use paging, the RTU must have the paging driver loaded (PAGINGxx.Dxx).
Figure: Pager Configuration Window for Telstra PET SMS paging in Australia.